Laserfiche WebLink
BACnet Communication Option Points List for 75T <br />Project: Climatec Energy - Mitch California Project 10/22/2015 <br />Prepared By: 10:52AM <br />AV:133 <br />Return Air Enthalpy <br />R <br />-20-10000 <br />rae_1 <br />RAE <br />AV:134 <br />Return Air Relative Humidity <br />W <br />% <br />0- 100 <br />rarh_1 <br />RARH <br />AV:135 <br />Return Air Temperature <br />W <br />dF <br />-40-240 <br />rat -1 <br />RAT <br />AV:137 <br />Space Temperature <br />W <br />dF <br />-40-240 <br />spt_1 <br />SPT <br />AV:138 <br />Space Temperature Offset <br />W <br />^F <br />-10-10 <br />spto_1 <br />SPTO <br />AV:139 <br />Space Temp Offset Range <br />W <br />5 <br />1 -10 <br />spto_rng_1 <br />SPTO_RNG <br />AV:143 <br />SP Reset Limit <br />W <br />0.75 <br />0-2 <br />sprlimit_1 <br />SPRLIMIT <br />AV:144 <br />SP Reset Ratio <br />W <br />0.2 <br />0 - 2 <br />sprratio_1 <br />SPRRATIO <br />AV:150 <br />Staged Gas LAT 1 <br />R <br />dF <br />-40-240 <br />latlsgas_1 <br />LAT1SGAS <br />AV:151 <br />Staged Gas LAT 2 <br />R <br />dF <br />-40-240 <br />lat2sgas_1 <br />LAT2SGAS <br />AV:152 <br />Staged Gas LAT 3 <br />R <br />dF <br />-40-240 <br />lat3sgas_1 <br />LAT3SGAS <br />AV:153 <br />Staged Gas LAT Sum <br />R <br />dF <br />-40-240 <br />lat_sgas_1 <br />LAT_SGAS <br />AV:154 <br />Staged Gas Limit Sw Temp <br />R <br />dF <br />-40-240 <br />Iimswtmp_l <br />LIMSWTMP <br />AV:156 <br />Stat. Pres. Reset Config <br />W <br />0 <br />0 - 4 <br />sprstcfg_1 <br />SPRSTCFG <br />AV:157 <br />Static Pressure Reset <br />W <br />0-15 <br />spreset_1 <br />SPRESET <br />AV:158 <br />Supply Air Setpnt. Reset <br />W <br />^F <br />0-20 <br />sasprset_l <br />SASPRSET <br />AV:159 <br />Temp Comp Start Cool Factor <br />W <br />min <br />0 <br />0-60 <br />tcstcool_l <br />TCSTCOOL <br />AV:160 <br />Temp Comp Start Heat Factor <br />W <br />min <br />0 <br />0-60 <br />tcstheat_1 <br />TCSTHEAT <br />AV:161 <br />Tempering in Cool SASP <br />W <br />dF <br />5-75 <br />tempcool_1 <br />TEMPCOOL <br />AV:162 <br />Tempering Purge SASP <br />W <br />dF <br />1-20-80 <br />temppurg_1 <br />TEMPPURG <br />AV:163 <br />Tempering Vent Occ SASP <br />W <br />dF <br />-20-80 <br />tempvocc_l <br />TEMPVOCC <br />AV:164 <br />Temper Vent Unocc <br />W <br />dF <br />-20-80 <br />tempvunc_l <br />TEMPVUNC <br />AV:166 <br />Un.Ec.Free Cool OAT Lock <br />W <br />dF <br />50 <br />40-70 <br />uefcntlo_1 <br />UEFCNTLO <br />AV:168 <br />Unoccupied Cool Mode End <br />R <br />0-100 <br />uccl_end 1 <br />UCCL_END <br />AV:169 <br />Unoccupied Cool Mode Start <br />R <br />0- 100 <br />ucclstrt_1 <br />UCCLSTRT <br />AV:170 <br />Unoccupied Heat Mode End <br />R <br />0- 100 <br />ucht_end_1 <br />UCHT_END <br />AV:171 <br />Unoccupied Heat Mode Start <br />R <br />0- 100 <br />uchtstrt_1 <br />UCHTSTRT <br />AV:172 <br />Unoc Econ Free Cool Cfg <br />W <br />0 <br />0 - 2 <br />uefc_cfg_l <br />UEFC_CFG <br />AV:173 <br />Unoc Econ Free Cool Time <br />W <br />min <br />120 <br />0-720 <br />uefctime_1 <br />UEFCTIME <br />AV:180 <br />VAV Occ. Cool Off Delta <br />W <br />deltaF <br />1 -25 <br />vavocoff_1 <br />VAVOCOFF <br />AV:181 <br />VAV Occ. Cool On Delta <br />W <br />deltaF <br />0-25 <br />vavocon_1 <br />VAVOCON <br />AV:183 <br />Vent Reheat RAT Offset <br />W <br />^F <br />0 <br />0 - 8 <br />dhvraoff_1 <br />DHVRAOFF <br />AV:184 <br />Vent Reheat Setpoint <br />W <br />dF <br />70 <br />55-95 <br />dhvht_sp_1 <br />DHVHT_SP <br />AV:186 <br />VFD/Act. Fire Speed/Pos. <br />W <br />% <br />100 <br />0-100 <br />bldgpfso_1 <br />BLDGPFSO <br />AV:187 <br />VFD-IGV Fire Speed Override <br />W <br />% <br />100 <br />0-100 <br />statpfso_l <br />STATPFSO <br />AV:188 <br />VFD Maximum Speed <br />W <br />% <br />100 <br />0-100 <br />statpmax_l <br />STATPMAX <br />AV:189 <br />VFD Minimum Speed <br />W <br />% <br />20 <br />0- 100 <br />statpmin_l <br />STATPMIN <br />AV:1003 <br />Outside Air Temperature <br />W <br />dF <br />1-40-240 <br />oat -1 <br />OAT <br />AV:1009 <br />IAQ - PPM Indoor CO2 <br />W <br />0-5000 <br />iaq_1 <br />IAQ <br />AV:1016 <br />Static Pressure <br />R <br />"H20 <br />-20-20 <br />static_press_l <br />SP <br />AV:1022 <br />HVAC Mode Numerical Form <br />R <br />0-40 <br />hvac_mode_1 <br />MODEHVAC <br />AV:1023 <br />Current Running Capacity <br />R <br />% <br />0- 100 <br />cool_capacity_1 <br />CAPTOTAL <br />AV:1024 <br />Cooling Control Point <br />R <br />dF <br />-20-140 <br />cool_ctrl_point_1 <br />COOLCPNT <br />AV:1025 <br />Heating Control Point <br />R <br />-20-140 <br />heat_ctrl_point_1 <br />HEATCPNT <br />AV:1027 <br />Leaving Air Temperature <br />R <br />dF <br />-40-240 <br />Ivg_air_temperature_1 <br />LAT <br />AV:1028 <br />Economizer Act. Curr. Pos <br />R <br />% <br />0- 100 <br />econ_pos_l <br />ECONOPOS <br />AV:1030 <br />Controlling Return Air Temp <br />W <br />dF <br />-40-240 <br />ra_temp_1 <br />RETURN_T <br />AV:1070 <br />Building Pressure <br />R <br />"H2O <br />-20-20 <br />bldg_static_press_l <br />BP <br />AV:1500 <br />Mixed Air Temperature <br />R <br />dF <br />-40-240 <br />ma_temp_l <br />MAT <br />AV:1600 <br />Cir A Suction Pressure <br />R <br />PSIG <br />-14-750 <br />suction_press_a_1 <br />SP_A <br />AV:1601 <br />Cir A Discharge Pressure <br />R <br />PSIG <br />1-14-750 <br />discharge_press_a_1 <br />DP_A <br />AV:1602 <br />Cir A Sat. Condensing <br />Temperature <br />R <br />dF <br />-40-240 <br />sat_cond_temp_a_l <br />SCTA <br />AV:1603 <br />Cir A Sat. Suction Temperature <br />R <br />dF <br />-40-240 <br />sat suction tem a 1 <br />SSTA <br />AV:1604 <br />Cir B Suction Pressure <br />R <br />PSIG <br />-14-750 <br />suction_press_b_1 <br />SP_B <br />AV:1605 <br />Cir B Discharge Pressure <br />R <br />PSIG <br />-14-750 <br />discharge_press_b_1 <br />DP_B <br />AV:1606 <br />Cir B Sat. Condensing <br />Temperature <br />R <br />dF <br />-40-240 <br />sat_cond_temp_b_l <br />SCTB <br />AV:1607 <br />Cir B Sat. Suction Temperature <br />R <br />dF <br />-40-240 <br />sat suction temp b 1 <br />SSTB <br />AV:2003 <br />Requested Heat Stage <br />R <br />0-20 <br />heat_run_1 <br />HT STAGE <br />AV:2007 <br />Controlling Space Temp <br />W <br />dF <br />-40-240 <br />space_temp_1 <br />SPACE_T <br />AV:2050 <br />I Supply Fan VFD Speed <br />R <br />% <br />0- 100 <br />sf vfd out ut 1 <br />SFAN VFD <br />AV:2075 <br />Exhaust Fan VFD Speed <br />R <br />% <br />0- 100 <br />ef_vfd_output_1 <br />EFAN_VFD <br />AV:2901 <br />User Defined Analog 1 <br />W <br />user_analog11 <br />Applied Rooftop Builder 3.19k Page 13 of 15 <br />