Laserfiche WebLink
903.2.7.1 High -piled storage—Amended. <br />An automatic sprinkler system shall be provided as required in Chapter 32 in all <br />buildings of Group M where storage of merchandise is in high -piled or rack <br />storage arrays. <br />903.2.9 Group S-1—Amended. <br />An automatic sprinkler system shall be provided throughout all buildings containing a <br />Group S-1 occupancy where one of the following conditions exists: <br />1. A Group S-1 fire area exceeds 7,500 square feet (697 m2). <br />2. A Group S-1 Fire area is located more than three stories above grade plane. <br />3. The combined area of all Group S-1 fire areas on all floors, including any <br />mezzanines, exceeds 5,000 square feet (2230 m2). <br />4. A Group S-1 Fire area used for the storage of commercial motor vehicles <br />where the fire area exceeds 5,000 square feet (464 m2). <br />5. A Group S-1 occupancy used for the storage of upholstered furniture or <br />mattresses exceeds 2,500 square feet (232 m2). <br />6. When the overall height of the building exceeds 45 feet. <br />903.2.9.1 Repair garages. <br />An automatic sprinkler system shall be provided throughout all buildings used as repair <br />garages in accordance with Section 406.8 of the California Building Code, as shown: <br />1. Buildings having two or more stories above grade plane, including basements, <br />with a fire area containing a repair garage exceeding 7,500 square feet (697 <br />m2). <br />2. Buildings not more than one story above grade plane, with a fire area <br />containing a repair garage exceeding 7,500 square feet (697 m2). <br />3. Buildings with repair garages servicing vehicles parked in basements. <br />4. A Group S-1 fire area used for the repair of commercial motor vehicles where <br />the fire area exceeds 5,000 square feet (465 m2). <br />903.2.9.2 Bulk storage of tires. <br />Buildings and structures where the area for the storage of tires exceeds 20,000 <br />cubic feet (566 m3) shall be equipped throughout with an automatic sprinkler <br />system in accordance with Section 903.3.1.1. <br />903.2.10 Group S-2 enclosed parking garages—Amended. <br />An automatic sprinkler system shall be provided throughout buildings classified as <br />enclosed parking garages in accordance with Section 406.6 of the California Building <br />Code where one of the following conditions exists: <br />1. Where the fire area of the enclosed parking garage exceeds 7,500 square feet <br />(697m2). <br />