Laserfiche WebLink
1905.1.9 ACI 318, Section 18.7.5.. Modify ACI 318, Section 18.7.5, by adding Section 18.7.5.8 and <br />18.7.5.9 as follows: <br /> <br />18.7.5.8 Where the calculated point of contra flexure is not within the middle half of the member <br />clear height, provide transverse reinforcement as specified in ACI 318 Sections 18.7.5.1, Items (a) <br />through (c), over the full height of the member. <br /> <br />18.7.5.9 At any section where the design strength, ϕPn, of the column is less than the sum of the <br />shears Ve computed in accordance with ACI 318 Sections 18.6.5.1 and 18.7.6.1.1 for all the beams <br />framing into the column above the level under consideration, transverse reinforcement as specified <br />in ACI 318 Sections 18.7.5.1 through 18.7.5.3 shall be provided. For beams framing into opposite <br />sides of the column, the moment components are permitted to be assumed to be of opposite sign. For <br />the determination of the design strength, ϕPn, of the column, these moments are permitted to be <br />assumed to result from the deformation of the frame in any one principal axis. <br /> <br />1905.1.10 ACI 318, Section 18.10.4. Modify ACI 318, Section 18.10.4, by adding Section 18.10.4.6 <br />to read as follows: <br /> <br />18.10.4.6 – Walls and portions of walls with Pu > 0.35Po shall not be considered to contribute to the <br />calculated shear strength of the structure for resisting earthquake-induced forces. Such walls shall <br />conform to the requirements of ACI 318 Section 18.14. <br /> <br />1905.1.11 ACI 318, Section 18.12.6. Modify ACI 318, Section 18.12.6.2, as follows: <br /> <br />18.12.6.2 Collector and boundary elements in topping slabs placed over precast floor and roof <br />elements shall not be less than 3 inches (76 mm) or 6 db in thickness, where db is the diameter of the <br />largest reinforcement in the topping slab. <br /> <br />Section 7-5-190: CONVENTIONAL LIGHT-FRAME CONSTRUCTION <br /> <br />Section 4.3.4 of SDPWS 2018 Edition is amended as follows: <br /> <br />Delete rows 5 & 6 of Table 4.3.4 <br /> <br />Section 2306.3 of the California Building Code, 2019 is amended as follows: <br /> <br />Section 2306.3 Wood –frame shear walls. Wood –frame shear walls shall be designed and <br />constructed in accordance with AWC SDPWS. Where panels are fastened to framing members with <br />staples, requirements and limitations of AWC SDPWS shall be met and the allowable shear values <br />set forth in Table 2306.3(1), 2306.3(2) or 2306.3(3) shall be permitted. The allowable shear values <br />in Tables 2306.3(1) and 2306.3(2) are permitted to be increased 40 percent for wind design. Panels <br />complying with ANSI/APA PRP-210 shall be permitted to use design values for Plywood Siding in <br />the AWC SDPWS. Shear walls sheathed with Portland cement plaster, gypsum lath, gypsum <br />sheathing or gypsum board shall not be used to resist seismic forces in structures assigned to Seismic <br />design Category D, E or F. <br /> <br />Section 2308.6.8.1 of the California Building Code, 2019 Edition is amended as follows: <br />