Location Existing Fixture Description kWQty Retrofit Code Description (Ltg control in RED)Hours kWh
<br />PRE-RETROFIT POST RETROFIT
<br />Qty kW SvdWt/Fxt kWh SvdHourskWhkWWt/Fxt
<br />Fire Station #12 -
<br /> (sorted by building, floor, area)
<br />City of San Leandro - Lighting Detail Report
<br />Building/Area:Main Building
<br />1st Floor
<br />1.65228 4,400 21 4,400281x4x 2L sm ind hood, F32T8 32w,
<br />electronic ballast
<br /> Rf#-1 Rm - Garage Bays 7,269 0.588 2,587 1.064 4,68259RLT842dw - (2) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />0.1182 4,400 21 4,40021x4x 2L wall wash, F32T8 32w,
<br />electronic ballast
<br /> Rf#-2 Rm - Garage Bays 519 0.042 185 0.076 33459RLT842dw - (2) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />0.2955 2,500 21 2,50051x4x 2L sm ind hood, F32T8 32w,
<br />electronic ballast
<br /> Rf#-3 Rm - shop work
<br />area
<br />738 0.105 262 0.19 47559RLT842dw - (2) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />0.1182 2,500 21 2,50021x4x 2L sm ind hood, F32T8 32w,
<br />electronic ballast
<br /> Rf#-4 Rm - laundry 295 0.042 105 0.076 19059RLT842dw - (2) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />0.4728 2,500 21 2,50081x4x 2L sm ind hood, F32T8 32w,
<br />electronic ballast
<br /> Rf#-5 Rm - weights 1,180 0.168 420 0.304 76059RLT842dw - (2) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />0.0591 500 21 50011x4x 2L sm ind hood, F32T8 32w,
<br />electronic ballast
<br /> Rf#-6 Rm - storage 30 0.021 10 0.038 1959RLT842dw - (2) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />0.3546 500 21 50062x4x 2L fxt, F32T8 32w, electronic
<br />ballast
<br /> Rf#-7 Rm - electrical
<br />room
<br />177 0.126 63 0.228 11459RLT842dw - (2) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />0.546 2,500 32 2,50062x4x 3L rec trf, F32T8 32w,
<br />electronic ballast
<br /> Rf#-8 Rm - Conf Room 1,350 0.189 472 0.351 87890RLT843dw - (3) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />0.186 2,500 11 2,5006CF 1L wm sonce, CFP-26w, CF
<br />ballast
<br /> Rf#-9 Rm - hallway 450 0.066 165 0.114 28530RL0111/h - (1) LED 4 pin lamp, direct wire, 120/277v,
<br />11w, 50,000-Hr L70 rated life
<br />0.182 2,500 32 2,50022x4x 3L rec trf, F32T8 32w,
<br />electronic ballast
<br /> Rf#-10 Rm - hallway 450 0.063 158 0.117 29290RLT843dw - (3) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />0.364 1,500 32 1,50042x4x 3L rec trf, F32T8 32w,
<br />electronic ballast
<br /> Rf#-11 Rm - Capitains
<br />Office
<br />540 0.126 189 0.234 35190RLT843dw - (3) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />0.364 500 32 50042x4x 3L rec trf, F32T8 32w,
<br />electronic ballast
<br /> Rf#-12 Rm - Capitans
<br />Sleeping area #1
<br />180 0.126 63 0.234 11790RLT843dw - (3) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />0.455 2,500 32 2,50052x4x 3L rec trf, F32T8 32w,
<br />electronic ballast
<br /> Rf#-13 Rm - front lobby 1,125 0.1575 394 0.2925 73190RLT843dw - (3) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />0.546 2,500 32 2,50062x4x 3L rec trf, F32T8 32w,
<br />electronic ballast
<br /> Rf#-14 Rm - TV/dining
<br />area
<br />1,350 0.189 472 0.351 87890RLT843dw - (3) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />0.1322 2,500 12 2,5002CF 2L rec can 6", CFP-26w, CF
<br />ballast
<br /> Rf#-15 Rm - TV/dining
<br />area
<br />330 0.024 60 0.108 27066RL012/ckit - (1) New LED recessed can kit, 12w,
<br />120/277v, 50,000-Hr rated life
<br />0.910 2,500 32 2,500102x4x 3L rec trf, F32T8 32w,
<br />electronic ballast
<br /> Rf#-16 Rm - kitchen 2,250 0.315 788 0.585 1,46290RLT843dw - (3) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />0.1182 2,000 21 2,00021x4x 2L sm wp, F32T8 32w,
<br />electronic ballast
<br /> Rf#-17 Rm - B/G RR 236 0.042 84 0.076 15259RLT842dw - (2) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />0.1182 2,500 21 2,50021x4x 2L sm wp, F32T8 32w,
<br />electronic ballast
<br /> Rf#-18 Rm - hallway 295 0.042 105 0.076 19059RLT842dw - (2) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />0.1182 2,000 21 2,00021x4x 2L sm wp, F32T8 32w,
<br />electronic ballast
<br /> Rf#-19 Rm - B/G RR 236 0.042 84 0.076 15259RLT842dw - (2) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />0.364 1,500 32 1,50042x4x 3L rec trf, F32T8 32w,
<br />electronic ballast
<br /> Rf#-20 Rm - Capitains
<br />Office
<br />540 0.126 189 0.234 35190RLT843dw - (3) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />0.364 500 32 50042x4x 3L rec trf, F32T8 32w,
<br />electronic ballast
<br /> Rf#-21 Rm - Capitans
<br />Sleeping area #2
<br />180 0.126 63 0.234 11790RLT843dw - (3) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />Fire Station #12 Lighting Page 14W* = wall switch sensor; C* = ceiling sensor; E* = existing sensor, L* Dimming Control 65
|