Location Existing Fixture Description kWQty Retrofit Code Description (Ltg control in RED)Hours kWh
<br />PRE-RETROFIT POST RETROFIT
<br />Qty kW SvdWt/Fxt kWh SvdHourskWhkWWt/Fxt
<br />Fire Station #9 -
<br /> (sorted by building, floor, area)
<br />City of San Leandro - Lighting Detail Report
<br />Building/Area:Main Building
<br />1st Floor
<br />0.2955 2,500 21 2,50052x4x 2L rec trf, F32T8 32w,
<br />electronic ballast
<br /> Rf#-1 Rm - weight room 738 0.105 262 0.19 47559RLT842dw - (2) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />1.88832 4,400 21 4,400321x4x 2L sm ind hood, F32T8 32w,
<br />electronic ballast
<br /> Rf#-2 Rm - garage bay 8,307 0.672 2,957 1.216 5,35059RLT842dw - (2) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />0.94416 4,400 21 4,400161x8x 2L sm ind hood, F32T8 32w,
<br />electronic ballast
<br /> Rf#-3 Rm - garage bay 4,154 0.336 1,478 0.608 2,67559RLT842dw - (2) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />0.0591 2,500 21 2,50011x4x 2L sm wp, F32T8 32w,
<br />electronic ballast
<br /> Rf#-4 Rm - hallway 148 0.021 52 0.038 9559RLT842dw - (2) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />0.0591 2,500 21 2,50011x4x 2L sm wp, F32T8 32w,
<br />electronic ballast
<br /> Rf#-5 Rm - laundry 148 0.021 52 0.038 9559RLT842dw - (2) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />0.2364 2,500 21 2,50041x4x 2L sm wp, F32T8 32w,
<br />electronic ballast
<br /> Rf#-6 Rm - Fitness Room 590 0.084 210 0.152 38059RLT842dw - (2) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />0.70812 2,500 21 2,500121x4x 2L sm strip cove, F32T8 32w,
<br />electronic ballast
<br /> Rf#-7 Rm - Fitness Room 1,770 0.252 630 0.456 1,14059RLT842dw - (2) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />0.182 2,500 32 2,50022x4x 3L rec trf, F32T8 32w,
<br />electronic ballast
<br /> Rf#-8 Rm - Front lobby 450 0.063 158 0.117 29290RLT843dw - (3) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />0.182 2,500 32 2,50022x4x 3L rec trf, F32T8 32w,
<br />electronic ballast
<br /> Rf#-9 Rm - reception
<br />desk area
<br />450 0.063 158 0.117 29290RLT843dw - (3) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />0.182 1,500 32 1,50022x4x 3L rec trf, F32T8 32w,
<br />electronic ballast
<br /> Rf#-10 Rm - Capt Office
<br />#1
<br />270 0.063 94 0.117 17690RLT843dw - (3) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />0.1182 1,500 21 1,50022x4x 2L ms box, F32T8 32w,
<br />electronic ballast
<br /> Rf#-11 Rm - Capt Office
<br />#1 Sleep area
<br />177 0.042 63 0.076 11459RLT842dw - (2) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />0.1182 950 21 95021x4x 2L sm wp, F32T8 32w,
<br />electronic ballast
<br /> Rf#-12 Rm - Capt Office
<br />#1 RR
<br />112 0.042 40 0.076 7259RLT842dw - (2) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />0.182 1,500 32 1,50022x4x 3L rec trf, F32T8 32w,
<br />electronic ballast
<br /> Rf#-13 Rm - Capt Office
<br />#2
<br />270 0.063 94 0.117 17690RLT843dw - (3) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />0.1182 1,500 21 1,50022x4x 2L ms box, F32T8 32w,
<br />electronic ballast
<br /> Rf#-14 Rm - Capt Office
<br />#2 Sleep area
<br />177 0.042 63 0.076 11459RLT842dw - (2) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />0.1182 950 21 95021x4x 2L sm wp, F32T8 32w,
<br />electronic ballast
<br /> Rf#-15 Rm - Capt Office
<br />#2 RR
<br />112 0.042 40 0.076 7259RLT842dw - (2) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />0.273 2,500 32 2,50032x4x 3L rec trf, F32T8 32w,
<br />electronic ballast
<br /> Rf#-16 Rm - turn out
<br />hallway
<br />675 0.0945 236 0.1755 43990RLT843dw - (3) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />0.273 500 32 50032x4x 3L rec trf, F32T8 32w,
<br />electronic ballast
<br /> Rf#-17 Rm - Dorm
<br />Room #1
<br />135 0.0945 47 0.1755 8890RLT843dw - (3) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />0.546 500 32 50062x4x 3L rec trf, F32T8 32w,
<br />electronic ballast
<br /> Rf#-18 Rm - Dorm
<br />Room #2
<br />270 0.189 94 0.351 17690RLT843dw - (3) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />0.2364 2,500 21 2,50041x4x 2L sm wp, F32T8 32w,
<br />electronic ballast
<br /> Rf#-19 Rm - Locker 590 0.084 210 0.152 38059RLT842dw - (2) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />0.2955 2,500 21 2,50051x4x 2L sm wp, F32T8 32w,
<br />electronic ballast
<br /> Rf#-20 Rm - Locker 738 0.105 262 0.19 47559RLT842dw - (2) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />0.546 2,500 32 2,50062x4x 3L rec trf, F32T8 32w,
<br />electronic ballast
<br /> Rf#-21 Rm - TV Room 1,350 0.189 472 0.351 87890RLT843dw - (3) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />Fire Station #9 Lighting Page 18W* = wall switch sensor; C* = ceiling sensor; E* = existing sensor, L* Dimming Control
<br />DocuSign Envelope ID: 64BB0189-33AC-48E9-B1D7-D912FB4998D8
|