Location Existing Fixture Description kWQty Retrofit Code Description (Ltg control in RED)Hours kWh
<br />PRE-RETROFIT POST RETROFIT
<br />Qty kW SvdWt/Fxt kWh SvdHourskWhkWWt/Fxt
<br />Main Library -
<br /> (sorted by building, floor, area)
<br />City of San Leandro - Lighting Detail Report
<br />0.182 3,500 32 3,50022x4x 3L rec trf PBLC, F32T8 32w,
<br />electronic ballast
<br /> Rf#-68 Rm - Mail Area 630 0.063 220 0.117 41090RLT843dw - (3) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballaste-oDS10
<br />0.182 3,500 32 3,50022x4x 3L rec trf PBLC, F32T8 32w,
<br />electronic ballast
<br /> Rf#-69 Rm - Concern
<br />Office
<br />630 0.063 220 0.117 41090RLT843dw - (3) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />0.091 3,500 32 3,50012x4x 3L rec trf PBLC, F32T8 32w,
<br />electronic ballast
<br /> Rf#-70 Rm - Locker 315 0.0315 110 0.0585 20590RLT843dw - (3) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />0.364 3,500 32 3,50042x4x 3L rec trf PBLC, F32T8 32w,
<br />electronic ballast
<br /> Rf#-71 Rm - Staff Area 1,260 0.126 441 0.234 81990RLT843dw - (3) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />0.54464 4,380 8 4,38064LED 1L rec can (GC), LED 8.5w
<br />R30, n/a
<br /> Rf#-112 Rm - Ext - Eve
<br />Mount
<br />2,383 0.544 2,383 0 08.5 DND - DND: (do not do, fixtures left as is)
<br />0.15318 4,380 8 4,38018LED 1L wm sconce (GC), LED 8.5w
<br />R30, n/a
<br /> Rf#-113 Rm - Ext - Eve
<br />Mount
<br />670 0.153 670 0 08.5 DND - DND: (do not do, fixtures left as is)
<br />0.15318 4,380 8 4,38018LED 1L wm wall sonce (GC), LED
<br />8.5w A19, n/a
<br /> Rf#-114 Rm - Ext - Eve
<br />Mount
<br />670 0.153 670 0 08.5 DND - DND: (do not do, fixtures left as is)
<br />0.22515 4,380 15 4,38015LED 1L rec can (City), LED 15w?,
<br />n/a
<br /> Rf#-115 Rm - Ext - Eve
<br />Mount
<br />986 0.225 986 0 015DND - DND: (do not do, fixtures left as is)
<br />0.59436 4,380 16 4,38036LED 1L rec ground mount (GC), LED
<br />16.5w A21, n/a
<br /> Rf#-116 Rm - Ext -
<br />Ground - Trees
<br />2,602 0.594 2,602 0 016.5 DND - DND: (do not do, fixtures left as is)
<br />0.04953 4,380 16 4,3803LED 1L rec ground mount (GC), LED
<br />16.5w A21, n/a
<br /> Rf#-117 Rm - Ext -
<br />Ground - Flag Poles
<br />217 0.0495 217 0 016.5 DND - DND: (do not do, fixtures left as is)
<br />0.04255 4,380 8 4,3805LED 1L rec ground mount (GC), LED
<br />8.5w A19, n/a
<br /> Rf#-118 Rm - Ext -
<br />Ground
<br />186 0.0425 186 0 08.5 DND - DND: (do not do, fixtures left as is)
<br />1.29616 4,380 81 4,38016LED 1L show box SqP BZ (VIS BSX),
<br />LED 81w, LED Driver 0-10v
<br /> Rf#-119 Rm - Ext - Pole
<br />Mount - Parking
<br />5,676 1.296 5,676 0 081DND - DND: (do not do, fixtures left as is)
<br />E-FSP211
<br />0.1623 4,380 54 4,3803LED 1L flood, BZ KM (VIS BSX), LED
<br />54w, LED Driver 0-10v
<br /> Rf#-120 Rm - Ext - Pole
<br />Mount - Parking
<br />710 0.162 710 0 054DND - DND: (do not do, fixtures left as is)
<br />E-FSP211
<br />2nd Floor
<br />0.546 2,500 32 2,50062x4x 3L rec trf PBLC, F32T8 32w,
<br />electronic ballast
<br /> Rf#-72 Rm - Conf Rm C 1,350 0.189 472 0.351 87890RLT843dw - (3) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />0.062 2,000 12 2,0002CF 1L rec can hz, CFP-26w, CF
<br />ballast
<br /> Rf#-73 Rm - Conf Rm C 120 0.024 48 0.036 7230RL012/ckit - (1) New LED recessed can kit, 12w,
<br />120/277v, 50,000-Hr rated life
<br />1.12217 4,400 12 4,40017CF 2L rec can hz, CFP-26w, CF
<br />ballast
<br /> Rf#-74 Rm - hallway
<br />area
<br />4,937 0.204 898 0.918 4,03966RL012/ckit - (1) New LED recessed can kit, 12w,
<br />120/277v, 50,000-Hr rated life
<br />0.728 2,500 32 2,50082x4x 3L rec trf PBLC, F32T8 32w,
<br />electronic ballast
<br /> Rf#-75 Rm - Conf Rm B 1,800 0.252 630 0.468 1,17090RLT843dw - (3) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />0.062 2,000 12 2,0002CF 1L rec can hz, CFP-26w, CF
<br />ballast
<br /> Rf#-76 Rm - Conf Rm B 120 0.024 48 0.036 7230RL012/ckit - (1) New LED recessed can kit, 12w,
<br />120/277v, 50,000-Hr rated life
<br />0.728 4,400 32 4,40082x4x 3L rec trf PBLC, F32T8 32w,
<br />electronic ballast
<br /> Rf#-77 Rm - Lobby 3,168 0.252 1,109 0.468 2,05990RLT843dw - (3) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />0.3966 4,400 12 4,4006CF 2L rec can hz, CFP-26w, CF
<br />ballast
<br /> Rf#-78 Rm - Lobby 1,742 0.072 317 0.324 1,42666RL012/ckit - (1) New LED recessed can kit, 12w,
<br />120/277v, 50,000-Hr rated life
<br />0.217 4,400 12 4,4007CF 1L rec can hz, CFP-26w, CF
<br />ballast
<br /> Rf#-79 Rm - Auditorium
<br />hallway
<br />924 0.084 370 0.126 55430RL012/ckit - (1) New LED recessed can kit, 12w,
<br />120/277v, 50,000-Hr rated life
<br />0.94416 2,500 21 2,500161x4x 2L sm strip, F32T8 32w,
<br />electronic ballast
<br /> Rf#-80 Rm - Room S228 2,360 0.336 840 0.608 1,52059RLT842dw - (2) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />Main Library Lighting Page 24W* = wall switch sensor; C* = ceiling sensor; E* = existing sensor, L* Dimming Control
<br />DocuSign Envelope ID: 64BB0189-33AC-48E9-B1D7-D912FB4998D8
|