Location Existing Fixture Description kWQty Retrofit Code Description (Ltg control in RED)Hours kWh
<br />PRE-RETROFIT POST RETROFIT
<br />Qty kW SvdWt/Fxt kWh SvdHourskWhkWWt/Fxt
<br />Main Library -
<br /> (sorted by building, floor, area)
<br />City of San Leandro - Lighting Detail Report
<br />0.182 3,510 32 3,51022x4x 3L rec trf PBLC, F32T8 32w,
<br />electronic ballast
<br /> Rf#-104 Rm - Room 209 632 0.063 221 0.117 41190RLT843dw - (3) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />0.364 3,510 32 3,51042x4x 3L rec trf PBLC, F32T8 32w,
<br />electronic ballast
<br /> Rf#-105 Rm - Room 210 1,264 0.126 442 0.234 82190RLT843dw - (3) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />0.1773 3,510 21 3,51031x4x 2L sm strip, F32T8 32w,
<br />electronic ballast
<br /> Rf#-106 Rm - Room 206 621 0.063 221 0.114 40059RLT842dw - (2) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />1.7157 3,510 12 3,51057CF 1L rec can hz, CFP-26w, CF
<br />ballast
<br /> Rf#-107 Rm - Library
<br />Main Room
<br />6,002 0.684 2,401 1.026 3,60130RL012/ckit - (1) New LED recessed can kit, 12w,
<br />120/277v, 50,000-Hr rated life
<br />6.93105 3,510 12 3,510105CF 2L rec can hz, CFP-26w, CF
<br />ballast
<br /> Rf#-108 Rm - Library
<br />Main Room
<br />24,324 1.26 4,423 5.67 19,90266RL012/ckit - (1) New LED recessed can kit, 12w,
<br />120/277v, 50,000-Hr rated life
<br />0.3069 3,510 18 3,51091x2x 1L rec wall wash, Biax 16",
<br />CF ballast
<br /> Rf#-109 Rm - Library
<br />Main Room
<br />1,074 0.162 569 0.144 50534RL0181/bx - (1) LED BIAX PL-L lamp, direct wire,
<br />120/277v, 18w, 16", 50,000-Hr L70 rated life
<br />10.915185 3,510 21 3,5101851x4x 2L pm ind/dir, F32T8 32w,
<br />electronic ballast
<br /> Rf#-110 Rm - Library
<br />Main Room
<br />38,312 3.885 13,636 7.03 24,67559RLT842dw - (2) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />3.5460 3,510 21 3,510601x4x 2L wm wall wash, F32T8
<br />32w, electronic ballast
<br /> Rf#-111 Rm - Library
<br />Main Room
<br />12,425 1.26 4,423 2.28 8,00359RLT842dw - (2) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />1,789 1,789Qty and kW for Main Library : 89.8
<br /> kWh for Main Library : 281,283
<br />31.9
<br />180,812
<br />57.9
<br />100,474
<br />Main Library Lighting Page 26W* = wall switch sensor; C* = ceiling sensor; E* = existing sensor, L* Dimming Control
<br />DocuSign Envelope ID: 64BB0189-33AC-48E9-B1D7-D912FB4998D8
|