Laserfiche WebLink
BACnet Communication Option Points List for 27T <br />Project: Climatec Energy - City of San Leandro 01/15/2016 <br />Prepared By: 02:54PM <br />NETWORK POINTS LIST (40/50A) <br />BACNET <br />OBJECT ID <br />POINTNAME <br />READ <br />ONLY <br />UNITS <br />DEFAULT <br />VALUE <br />RANGE <br />BACNET <br />OBJECTNAME <br />UNIT <br />POINT <br />AV:9 <br />Active Demand Limit <br />W <br />% <br />n/a <br />0-100 <br />dem lim 1 <br />DEM LIM <br />AV:10 <br />Air Temp Lvg Supply Fan <br />R <br />°F <br />n/a <br />n/a <br />sat—1 <br />SAT <br />AV:11 <br />CEM AN 1 4-20 ma J5,1-2 <br />W <br />mA <br />n/a <br />0-20 <br />cem4201 1 <br />CEM4201 <br />AV:12 <br />CEM AN 1OKtemp J5,1-2 <br />W <br />°F <br />n/a <br />-40-240 <br />cem10k1 1 <br />CEM10K1 <br />AV:13 <br />CEM AN2 4-20 ma J5,3-4 <br />W <br />mA <br />n/a <br />0-20 <br />cem4202 1 <br />CEM4202 <br />AV:14 <br />CEM AN2 1 OK temp J5,3-4 <br />W <br />°F <br />n/a <br />-40-240 <br />cem10k2 1 <br />CEM10K2 <br />AV:15 <br />Temper Supply Air Setpt <br />W <br />°F <br />n/a <br />0-100 <br />sasptemp_1 <br />SASPTEMP <br />AV:16 <br />BP PID Evaluation Time Level <br />W <br />min <br />1 <br />0-10 <br />bpperiod_1 <br />BPPERIOD <br />AV:17 <br />BP Setpoint Offset <br />W <br />in H2O <br />0.05 <br />0-0.5 <br />b so 1 <br />BPSO <br />AV:18 <br />BP Threshold Adjustment <br />W <br />n/a <br />1 <br />0.1-10 <br />bpz_gain_l <br />BPZ GAIN <br />AV:22 <br />Capacity Load Factor <br />R <br />% <br />n/a <br />n/a <br />smz 1 <br />SMZ <br />AV:23 <br />Capacity Threshold Adj <br />W <br />n/a <br />1 <br />0-10 <br />z qain 1 <br />Z GAIN <br />AV:24 <br />Compressor Al Run Hours <br />R <br />hr <br />n/a <br />n/a <br />hr a1 1 <br />HR Al <br />AV:25 <br />Compressor Al Starts <br />R <br />n/a <br />n/a <br />n/a <br />cy_al_l <br />CY Al <br />AV:26 <br />Compressor Al Strikes <br />R <br />n/a <br />n/a <br />n/a <br />cm al str 1 <br />CMPA1 STR <br />AV:27 <br />Compressor Al Timeguard <br />R <br />n/a <br />n/a <br />n/a <br />cmpal_tg_1 <br />CMPA1 TG <br />AV:28 <br />Compressor A2 Run Hours <br />R <br />hr <br />n/a <br />n/a <br />hr—a2-1 <br />HR A2 <br />AV:29 <br />Compressor A2 Starts <br />R <br />n/a <br />n/a <br />n/a <br />c a2 1 <br />CY A2 <br />AV:30 <br />Compressor A2 Strikes <br />R <br />n/a <br />n/a <br />n/a <br />cmpa2str_l <br />CMPA2STR <br />AV:31 <br />Compressor A2 Timeguard <br />R <br />n/a <br />n/a <br />n/a <br />cmpa2_tg_1 <br />CMPA2 TG <br />AV:32 <br />Compressor B1 Run Hours <br />R <br />hr <br />n/a <br />n/a <br />hr bl 1 <br />HR B1 <br />AV:33 <br />Compressor B1 Starts <br />R <br />n/a <br />n/a <br />n/a <br />c b1 1 <br />CY 131 <br />AV:34 <br />Compressor 131 Strikes <br />R <br />n/a <br />n/a <br />n/a <br />cmpblstr_1 <br />CMPB1STR <br />AV:35 <br />Compressor B1 Timeguard <br />R <br />I n/a <br />n/a <br />n/a <br />cm bl t -1 <br />CMPB1 TG <br />AV:36 <br />Compressor B2 Run Hours <br />R <br />hr <br />n/a <br />n/a <br />hr b2-1 <br />HR B2 <br />AV:37 <br />Compressor B2 Starts <br />R <br />n/a <br />n/a <br />n/a <br />cy_b2_1 <br />CY B2 <br />AV:38 <br />Compressor B2 Strikes <br />R <br />n/a <br />n/a <br />n/a <br />cm b2str 1 <br />CMPB2STR <br />AV:39 <br />Compressor B2 Timeguard <br />R <br />n/a <br />n/a <br />n/a <br />cm b2 to 1 <br />CMPB2 TG <br />AV:40 <br />Compressor Lockout Temp <br />W <br />°F <br />40 <br />-20-55 <br />oaticomp_1 <br />OATLCOMP <br />AVAIL <br />Cool Trend Demand Level <br />W <br />°^F <br />0.1 <br />0.1-5 <br />ctrendly 1 <br />CTRENDLV <br />AV:42 <br />Cool Trend Time (secs) <br />W <br />sec <br />120 <br />30-600 <br />ctrendtm 1 <br />CTRENDTM <br />AVA3 <br />Ctl.Temp RAT,SPT or ZONE <br />R <br />°F <br />n/a <br />n/a <br />ctrltemp_1 <br />CTRLTEMP <br />AVA4 <br />Current Running Capacity <br />R <br />% <br />n/a <br />n/a <br />hts ca 1 <br />HTSG CAP <br />AV:45 <br />DAQ PPM Fan Off Setpoint <br />W <br />n/a <br />200 <br />0-2000 <br />da fnoff 1 <br />DAQFNOFF <br />AVA6 <br />DAQ PPM Fan On Setpoint <br />W <br />n/a <br />400 <br />0-2000 <br />dagfnon_l <br />DAQFNON <br />AVA9 <br />Dehumidify Cool Setpoint <br />W <br />°F <br />45 <br />40-55 <br />dhcools 1 <br />DHCOOLSP <br />AV:50 <br />Dehumidify RH Setpoint <br />W <br />% <br />55 <br />10-90 <br />dhrelhsp_l <br />DHRELHSP <br />AV:52 <br />Demand Limit Select <br />W <br />n/a <br />0 <br />0-3 <br />dmd ctrl 1 <br />DMD CTRL <br />Applied Rooftop Builder 3.19m Page 10 of 48 <br />