File Number: 16-629 <br />the shears Ve computed in accordance with ACI 318 Sections 18.6.5.1 and 18.7.6.1.1 for all <br />the beams framing into the column above the level under consideration, transverse <br />reinforcement as specified in ACI 318 Sections 18.7.5.1 through 18.7.5.3 shall be provided. <br />For beams framing into opposite sides of the column, the moment components are permitted <br />to be assumed to be of opposite sign. For the determination of the design strength, jPn, of <br />the column, these moments are permitted to be assumed to result from the deformation of the <br />frame in any one principal axis. <br />1905.1.10 ACI 318, Section 18.10.4. Modify ACI 318, Section 18.10.4, by adding Section <br />18.10.4.6 to read as follows: <br />18.10.4.6 - Walls and portions of walls with Pu > 0.35Po shall not be considered to contribute <br />to the calculated shear strength of the structure for resisting earthquake-induced forces. Such <br />walls shall conform to the requirements of ACI 318 Section 18.14. <br />1905.1.11 ACI 318, Section 18.12.6. Modify ACI 318, Section 18.12.6.2, as follows: <br />18.12.6.2 Collector and boundary elements in topping slabs placed over precast floor and roof <br />elements shall not be less than 3 inches (76 mm) or 6 db in thickness, where db is the <br />diameter of the largest reinforcement in the topping slab. <br />Section 7-5-190: CONVENTIONAL LIGHT-FRAME CONSTRUCTION <br />Section 4.3.4 of SDPWS 2015 Edition is amended as follows: <br />Delete rows 5 & 6 of Table 4.3.4 <br />Section 2306.3 of the California Building Code, 2016 is amended as follows: <br />Section 2306.3 Wood -frame shear walls. Wood -frame shear walls shall be designed and <br />constructed in accordance with AWC SDPWS. Where panels are fastened to framing <br />members with staples, requirements and limitations of AWC SDPWS shall be met and the <br />allowable shear values set forth in Table 2306.3(1), 2306.3(2) or 2306.3(3) shall be permitted. <br />The allowable shear values in Tables 2306.3(1) and 2306.3(2) are permitted to be increased <br />40 percent for wind design. Panels complying with ANSI/APA PRP-210 shall be permitted to <br />use design values for Plywood Siding in the AWC SDPWS. Shear walls sheathed with <br />Portland cement plaster, gypsum lath, gypsum sheathing or gypsum board shall not be used <br />to resist seismic forces in structures assigned to Seismic design Category D, E or F. <br />Section 2308.6.8.1 of the California Building Code, 2016 Edition is amended as follows: <br />Section 2308.6.8.1 Foundation Requirements. Braced wall lines shall be supported by <br />continuous foundations. <br />Exceptions: <br />1. One-story buildings with maximum plan dimension not exceeding 50 feet (15240 <br />mm), may have continuous foundations located at exterior braced wall lines <br />only. <br />Page 11 City of San Leandro Printed on 11/15/2016