Location Existing Fixture Description kWQty Retrofit Code Description (Ltg control in RED)Hours kWh
<br />PRE-RETROFIT POST RETROFIT
<br />Qty kW SvdWt/Fxt kWh SvdHourskWhkWWt/Fxt
<br />San Leandro Aquatic Center -
<br /> (sorted by building, floor, area)
<br />City of San Leandro - Lighting Detail Report
<br />Building/Area:Main Building
<br />1st Floor
<br />0.0862 500 24 50021x3x 2L wm vapor tight, F25T8
<br />25w, electronic ballast
<br /> Rf#-1 Rm - Chlorine Strg
<br />(Ext South End)
<br />43 0.048 24 0.038 1943RLT832dw - (2) 3' LED T8 lamp 10w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />0.0862 500 24 50021x3x 2L wm vapor tight, F25T8
<br />25w, electronic ballast
<br /> Rf#-2 Rm - Acid Storage
<br />(Ext South End)
<br />43 0.048 24 0.038 1943RLT832dw - (2) 3' LED T8 lamp 10w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />1.06218 500 21 500181x4x 2L sm vapor tight, F32T8
<br />32w, electronic ballast
<br /> Rf#-3 Rm - Pool
<br />Equipment (Ext South
<br />531 0.378 189 0.684 34259RLT842dw - (2) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />0.072 2,900 12 2,9002CF 1L rec can V, CFP-32w, CF
<br />ballast
<br /> Rf#-4 Rm - Main Entry
<br />desk
<br />203 0.024 70 0.046 13335RL012/ckit - (1) New LED recessed can kit, 12w,
<br />120/277v, 50,000-Hr rated life
<br />0.48 2,900 5 2,9008QH 1L pm cone, Inc. 50w mini
<br />Bpin, n/a
<br /> Rf#-5 Rm - Main Entry
<br />desk
<br />1,160 0.04 116 0.36 1,04450RL051/bpin - (1) LED 5w mini-bipin lamp, 4000K
<br />0.2364 2,900 21 2,90041x4x 2L wm wall wash, F32T8
<br />32w, electronic ballast
<br /> Rf#-6 Rm - hallway 684 0.084 244 0.152 44159RLT842dw - (2) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />1.41624 2,600 21 2,600241x4x 2L wm wall wash, F32T8
<br />32w, electronic ballast
<br /> Rf#-7 Rm - B RR/locker 3,682 0.504 1,310 0.912 2,37159RLT842dw - (2) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />0.0862 2,600 24 2,60021x3x 2L wm wall wash, F25T8
<br />25w, electronic ballast
<br /> Rf#-8 Rm - B RR/locker 224 0.048 125 0.038 9943RLT832dw - (2) 3' LED T8 lamp 10w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />0.216 2,600 12 2,6006CF 1L rec can V, CFP-32w, CF
<br />ballast
<br /> Rf#-9 Rm - B RR/locker 546 0.072 187 0.138 35935RL012/ckit - (1) New LED recessed can kit, 12w,
<br />120/277v, 50,000-Hr rated life
<br />0.288 2,600 12 2,6008CF 1L rec can V, CFP-32w, CF
<br />ballast
<br /> Rf#-10 Rm - B RR/locker
<br />shower
<br />728 0.096 250 0.184 47835RL012/ckit - (1) New LED recessed can kit, 12w,
<br />120/277v, 50,000-Hr rated life
<br />0.1182 500 21 50021x4x 2L sm strip, F32T8 32w,
<br />electronic ballast
<br /> Rf#-11 Rm - hot water
<br />heater
<br />59 0.042 21 0.076 3859RLT842dw - (2) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />1.0089 1,200 42 1,20094x4x 4L rec trf volumetric, F32T8
<br />32w, electronic ballast
<br /> Rf#-12 Rm - Events
<br />Room
<br />1,210 0.378 454 0.63 756112RLT844dw - (4) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />0.1053 1,200 12 1,2003CF 1L rec can V, CFP-32w, CF
<br />ballast
<br /> Rf#-13 Rm - Events
<br />Room
<br />126 0.036 43 0.069 8335RL012/ckit - (1) New LED recessed can kit, 12w,
<br />120/277v, 50,000-Hr rated life
<br />0.1182 500 21 50021x4x 2L sm wp, F32T8 32w,
<br />electronic ballast
<br /> Rf#-14 Rm - Events
<br />Room Storage #1
<br />59 0.042 21 0.076 3859RLT842dw - (2) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />0.1182 500 21 50021x4x 2L sm wp, F32T8 32w,
<br />electronic ballast
<br /> Rf#-15 Rm - Events
<br />Room Storage #2
<br />59 0.042 21 0.076 3859RLT842dw - (2) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />1.41624 2,600 21 2,600241x4x 2L wm wall wash, F32T8
<br />32w, electronic ballast
<br /> Rf#-16 Rm - G RR/locker 3,682 0.504 1,310 0.912 2,37159RLT842dw - (2) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />0.0862 2,600 24 2,60021x3x 2L wm wall wash, F25T8
<br />25w, electronic ballast
<br /> Rf#-17 Rm - G RR/locker 224 0.048 125 0.038 9943RLT832dw - (2) 3' LED T8 lamp 10w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />0.216 2,600 12 2,6006CF 1L rec can V, CFP-32w, CF
<br />ballast
<br /> Rf#-18 Rm - G RR/locker 546 0.072 187 0.138 35935RL012/ckit - (1) New LED recessed can kit, 12w,
<br />120/277v, 50,000-Hr rated life
<br />0.288 2,600 12 2,6008CF 1L rec can V, CFP-32w, CF
<br />ballast
<br /> Rf#-19 Rm - G RR/locker
<br />shower
<br />728 0.096 250 0.184 47835RL012/ckit - (1) New LED recessed can kit, 12w,
<br />120/277v, 50,000-Hr rated life
<br />0.1182 500 21 50021x4x 2L sm strip, F32T8 32w,
<br />electronic ballast
<br /> Rf#-20 Rm - hot water
<br />heater
<br />59 0.042 21 0.076 3859RLT842dw - (2) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />0.1182 500 21 50021x4x 2L sm wp, F32T8 32w,
<br />electronic ballast
<br /> Rf#-21 Rm - supply
<br />room
<br />59 0.042 21 0.076 3859RLT842dw - (2) 4' LED T8 lamp 10.5w, Type B, Direct
<br />Wire, 50,000-Hr L70 rated life, remove existing ballast
<br />San Leandro Aquatic Center Lighting Page 40W* = wall switch sensor; C* = ceiling sensor; E* = existing sensor, L* Dimming Control
<br />DocuSign Envelope ID: 64BB0189-33AC-48E9-B1D7-D912FB4998D8
|