3. Alarms <br /> a. Alarms shall be routed directly from Network Automation Engines to PCs and <br /> servers. It shall be possible for specific alarms from specific points to be routed <br /> to specific PCs and servers. The alarm management portion of the user interface <br /> shall, at the minimum, provide the following functions: <br /> 0 Log date and time of alarm occurrence. <br /> 0 Generate a "Pop -Up" window, with audible alarm, informing a user that <br /> an alarm has been received. <br /> 0 Allow a user, with the appropriate security level, to acknowledge, <br /> temporarily silence, or discard an alarm. <br /> 0 Provide an audit trail on hard drive for alarms by recording user <br /> acknowledgment, deletion, or disabling of an alarm. The audit trail shall <br /> include the name of the user, the alarm, the action taken on the alarm, <br /> and a time /date stamp. <br /> 0 Provide the ability to direct alarms to an e-mail address or alphanumeric <br /> pager. This must be provided in addition to the pop up window <br /> described above. Systems that use e-mail and pagers as the exclusive <br /> means of annunciating alarms are not acceptable. <br /> 0 Any attribute of any object in the system may be designated to report an <br /> alarm. <br /> b. The BMS shall annunciate diagnostic alarms indicating system failures and <br /> non - normal operating conditions. <br /> c. The BMS shall allow a minimum of 4 categories of alarm sounds customizable <br /> through user defined way.files. <br /> d. The BMS shall annunciate application alarms at minimum, as required by Part <br /> 3. <br /> 4. Reports and Summaries <br /> a. Reports and Summaries shall be generated and directed to the user interface <br /> displays, with subsequent assignment to printers, or disk. As a minimum, the <br /> system shall provide the following reports: <br /> 0 All points in the BMS <br /> 0 All points in each BMS application <br /> 0 All points in a specific controller <br /> 0 All points in a user - defined group of points <br /> 0 All points currently in alarm <br /> 0 All points locked out <br /> 0 All BMS schedules <br /> 0 All user defined and adjustable variables, schedules, interlocks and the <br /> like. <br /> b. Summaries and Reports shall be accessible via standard Ul functions and not <br /> dependent upon custom programming or user defined HTML pages. <br /> Non - Professional Services Agreement between November 1, 2010 <br /> City of San Leandro and Martin Industries, Inc., OBA Climatech Page 15 of 28 <br />