Laserfiche WebLink
occupancy, sq./ft., number of floors, height of building, setbacks to property lines, <br />frontage increases, fire sprinkler type, and fire alarm type. <br />4. A Fire Sprinkler system is required. Provide a "Deferred Submittal' heading on <br />the cover sheet for the Fire Sprinkler system. <br />5. A Life Safety Fire Alarm system is required. Provide a "Deferred Submittal' <br />heading on the cover sheet for the Life Safety Fire Alarm system. <br />6. Provide a "Deferred Submittal' heading on the cover sheet for the Underground <br />Fire Line. <br />7. Water flow data shall be provided to ensure adequate fire flow is available and <br />adequate hydrants are provided. A Fire Pump shall be provided if necessary, <br />based on water flow data. A "Deferred Submittal' heading on the cover sheet for <br />the Fire Pump shall be provided, if required. <br />8. A stand -pipe system is required in the stairwells. <br />9. Hose cabinets maybe required in the hallways if access to any location exceeds <br />130 feet. <br />10. Fire Lanes (Fire Access Routes) shall be a minimum of 26 feet in width when the <br />building is over 30 feet in height. <br />11. If an electric gate is installed, a Knox box key switch shall be provided for Fire <br />Department access <br />12. Fire Department access to the roof shall be provided. <br />13. Carbon monoxide detection shall be provided for fuel fired appliances, as <br />required per code. <br />14. Elevator cars shall be gurney accessible. <br />15. Elevator shaft protection shall be provided (Lobby, door, or other form of shaft <br />protection). <br />16. Knox boxes shall be installed at stairwells and electrical rooms for Fire <br />Department access. <br />17. 2A 10B:C fire extinguishers shall be provided with maximum travel distance of <br />75 feet. <br />18. Interior climate control shall be provided. <br />19. A deferred submittal shall be made for the installation of solar and perimeter <br />access. <br />20. Emergency lighting shall be provided in all common areas with an average of 1- <br />foot candle at the floor along the means of egress route and to the public way. <br />21. Illuminated Exit signs shall be provide identifying the means of egress route. <br />22. Low level exit signs shall be provided in the corridors. <br />23.All stairway floors shall be identified with signs as well the stairwell with roof <br />access. <br />Agreement to Conditions August 3, 2021 <br />PLN20-0022 15693 E. 14th Street Page 11 of 20 <br />